| |
| DC fan general specification : |
| |
| |
1. |
Operation temperature: |
| |
|
-10 ℃ to + 70 ℃ . (humidity: 35%~85%RH) |
| |
|
|
| |
2. |
Storage temperature: |
| |
|
-40 ℃ to + 75 ℃ . (humidity: 35%~85%RH) |
| |
|
|
| |
3. |
Insulation resistance: |
| |
|
10mega OHM MIN. At 500VDC (between frame and (+) terminal) |
| |
|
|
| |
4. |
Dielectric strength: |
| |
|
5mA MAX. at 500 VAC 60 Hz one minute (between frame and (+) terminal) |
| |
|
|
| |
5. |
Vibration resistance test: |
| |
|
Applied 5.30Hz, 0.04 peak to peak amplitude, 30-500Hz, 2G peak amplitude for five minutes to all three axis. |
| |
|
Fan shall satisfy the specified performance standards. |
| |
|
|
| |
6. |
Shock test: |
| |
|
Under the conditions of 60G , 11 ms (1/2 sine), two times to all three axis, it shall satisfy the specified performances standards. |
| |
|
|
| |
7. |
Protection: |
| |
|
(1) Impedance protection: The rotor drive shall be restricted for 72 hours in the state where is made in the |
| |
|
range of operating temperature and operating voltage. In shall not fail. |
| |
|
(2) Locked current protection:DC fan has over current protection circuit with auto restart after after 3 seconds. |
| |
|
|
| |
8. |
Life expected: |
| |
|
Mean endurance time until the revolution drops by 30% of the initial value in the condition of continuously running under |
| |
|
standard environmental condition and rated condition. |
| |
|
|
| |
9. |
Polarity protection: |
| |
|
The fan will not cause damage when reverse rated voltage is connected. |
|
|
|
Noise characteristics: |
| |
| |
Noise measurements are central values as measured at a point 1m from the suction surface of a fan suspended |
| |
and at rated voltage in an anechoic room with LARSON DAVIS type 824s sound level meter. |
| |
|
| |
|
| |
|
|
|
Air flow and static pressure characteristics: |
|
| |
The performance including air flow and air pressure measured at rated voltage in double chamber is measured |
| |
according to AMCA 210-99 standard as shown below: |
| |
|
| |
|
| |
|
|
| Conversion table: |
| |
| |
Static pressure: |
Air flow: |
| |
1 mm H 2 O= 0.0394 inch H 2 O |
1 m 3 /min= 35.31 ft 3 /min (CFM) |
| |
1 mm H 2 O= 9.8 Pa (Pascal) |
1 CFM= 0.0283 m 3 /min |
| |
1 inch H 2 O= 25.4mm H 2 O |
1 m 3 /min= 16.67 I/sec |
| |
1 inch H 2 O= 249 Pa |
1 CFM= 0.472 I/sec |
| |
|
1 I/sec= 0.06 m 3 /min |
| |
|
|
|
| Signal & control: Frequency generator (FG) signal |
|
| |
Pulse sensor produce two-cycle rectangular waves per rotation of fan motor. These are best suited for |
| |
detecting rotating speeds. Pulse sensors can be incorporated in all kinds of DC fans motors. |
| |
|
| |
Output circuit : |
Specifications : |
| |
 |
Output type: open collect |
| |
VFG maximum voltage |
| |
◎13.8V as 12V Voltage fans |
| |
◎26.4V as 24V Voltage fans |
| |
◎56.0V as 48V Voltage fans |
| |
Ic maximum current= 5mA |
| |
Output waveform : |
| |
During normal run |
|
| |
 |
T= T1+T2+T3+T4= 60/N (Sec) |
| |
N: SPEED (RPM) |
| |
|
|
| |
Rotation detector (RD) signal: |
| |
|
 |
| PWM (pulse width modulation): |
| |
| |
In PWM speed control, a fixed frequency square wave is applied to the speed control of the fan. |
| |
The ratio of the on time vs. the PWM period is proportional to the RPM. |
| |
To control signal line of the fan, the frequency of PWM shall be able to accept a 30 HZ to 30kHz. |
| |
The preferred operating point for the fan is 0%~100% duty cycle. |
|
| |
Using Fan by Parnell and Series arrangement : |
| |
| |
Estimate Fan Air flow and Pressure |
| |
 |
| |
For identical fans in parallel, P max = P max,single, Q max = Q max,single x no.of fans |
|
|
| Fan Choice by Your System Impendence : |
| |
| |
 |
| |
Every system has an impedance curve. System impedance is generally proportional to Q2. |
| |
Operating point is the intersection of P-Q curve and the impedance curve. The use of impedance |
| |
curves is to select a fan that provides maximum air flow rate at the operating point. |
| |
|
|